The 15KV pole mounted disconnect switch is made of proven durable, corrosion-resistant material. (304L stainless steel plate for warships), ensure a long service life (30years), our 15kv load break switch can carry out a series of operations, with the pole top equipment ideal characteristics.
Each GOPOWER 15kv load break switch has been filled with sf6 gas before leaving the factory, sealed treatment. The 15 kv pole mounted disconnect switch test was carried out according to IEC60265-1 (1988) GB 3804-1990 standard.
15kv load break switch has a certain interrupting capacity because of the interrupting device, but 15 kv pole mounted disconnect switch is not as strong as the interrupting capacity of the circuit breaker, which can split the normal working current, and in the case of short circuit, he can only silently withstand the short circuit current, and if this time the manual or electric breaking may explode, so the load switch is generally used together with the current limiting fuse (load switch + fuse is not the standard configuration, and can also be used without fuse) In the event of an overload or short circuit, the circuit is broken by a fuse. In order to save costs, the load switch + fuse can replace the circuit breaker. Inquiry more pole top switches
Products Type | FWX-15 |
Basic Ratings | |
Maximum System Voltage | 15KV |
Rated Continuous Current | 630A |
Rated Frequency | 50/60Hz |
Short Time Withstand Current | IKA/sec |
Making and Breaking Capacity | |
Mainly Active LoadCurrent | 630A |
Number of Load-break Operations | 400times |
Short-circuit Making Current(peak) | 50KA |
Number of Making Operations | 5 times |
Cable Charging Current | lOA |
Line Charging Current | lOA |
Closed Loop Circuit Current | 630A |
Transformer Magnetizing Current | 22A |
Power Frequency Withstand Current Test | |
Wet Condition- 10 sec (Ph- Ph-Eth, Across Interrupters) | 50KV |
DryCondition- I min ( Phase to Phase, Phase to Earth) | 50KV |
Dry Condition - 1 min (Across Interrupter ) | 60KV |
Impulse Withstand Current Test(1.2 x 50 µs) |
Internal Arc Test | 20kA /0.1 sec |
Arc Extinction Medium | SF6 Gas |
Insulation Medium | SF6 Gas |
Creepage Distance (Porcelain) | 560mm |
IP Level | 54 |
Operation Performance | |
Closing/Opening Tin | < O. l sec |
Mechanica l Operations (Guaranteed) | l OOOO times |
Operating Temperature.1re(*Manual Type) | -25~+70℃ |
Gas Pressure | |
Nominal Pressure (kg/cm2 G, at 20°C) | 0.07 |
Bursting Pressure (kg/cm2 G) | 4 ~ 6 |
Minimum Gas Pressure (kg/cm2 G) | 0.0 |
Leakage Rate (cc/ sec) | 1% |
Other Ratings & Specifications | |||
Internal Arc Test | 20kA /0.1 sec | 20kA /0.1 sec | 20kA /0.1 sec |
Arc Extinction Medium | SF6 Gas | SF6 Gas | SF6 Gas |
Insulation Medium | SF6 Gas | SF6 Gas | SF6 Gas |
Creepage Distance (Porcelain) | 380mm | 700mm | 1055mm |
Creepage Distance (Silicon) | 780mm | 1200mm | 1550mm |
Dry arcing distance | ≥200mm | ≥ | ≥ |
IP Level | 65 | 65 | 65 |
Operation Performance | |||
Closing/Opening Time | <1sec | <1sec | <1sec |
Mechanical Operations (Guaranteed) | 10000times | 10000times | 10000times |
Operating Temperature (*Manual Type) | -25~+70℃ | -25~+70℃ | -25~+70℃ |
Gas Pressure | |||
Nominal Pressure (MPa, at 20°C) | 0.07 | 0.07 | 0.07 |
Bursting Pressure (MPa) | 0.4~0.6 | 0.4~0.6 | 0.4~0.6 |
Minimum Gas Pressure (MPa) | 0.05 | 0.05 | 0.05 |
Leakage Rate (cc/ sec) | ≤0.5% | ≤0.5% | ≤0.5% |
Voltage sensors | |||
CT ABC 10P10 5VA | 400:5 | 400:5 | 400:5 |
Incoming side and outgoing side of the voltage sensor | 6 Voltage sensor(built-in) Phase voltage:(24(36)kV/√3)/(3.25V/√3) | ||
Special attention should be paid to the voltage sensor, which must be directly fed by the 15kv load break pole mounted disconnect switch. No additional adjustment circuit can be added to the controller. The voltage signal of the switch into the test line needs to be tested separately. |
Related Products
Contact Us
Start Your Partnership With Gopower