The 11 kv outdoor vacuum circuit breaker is equipped with one integrated current transformer per pole. The current transformer has a ratio of 600 A:5A.
VCB rating for 11kv Recloser is for protection purposes and optimized for operation with the controller. For more pole top switches at bulk price.
Products Type | ZW32-12 |
Maximum System Voltage | 12kV |
Rated Continuous Current | 630A |
Rated Frequency | 50/60Hz |
Short Time Withstand Current | 20kA/1sec |
Mainly Active Load Current | 630A |
Number of Load-break Operations | 30 |
Short-circuit Making Current (peak) | 50kA |
Number of Making Operations | 5 times |
Cable Charging Current | 25A |
Line Charging Current | 1.5A |
Closed Loop Circuit Current | 630A |
Transformer Magnetizing Current | 22A |
Wet Condition-10sec Ph- Ph-Eth, Across Interrupters | 45kV |
DryCondition-1min,Ph- Ph, Phase to Earth | 42kV |
Dry Condition - 1 min AcrossInterrupter | 48kV |
Phase to Phase, Phase to Earth | 75kV |
Across Interrupter | 85kV |
Internal Arc Test | 20kA /0.1 sec |
Arc Extinction Medium | vacuum |
Insulation Medium | vacuum |
Creepage Distance (Silicon) | 780mm |
Dry arcing distance | ≥200mm |
IP Level | 67 |
Closing/Opening Time | <1sec |
Mechanical Operations (Guaranteed) | 10000times |
Operating Temperature (*Manual Type) | -25~+70℃ |
Related Products
Contact Us
Start Your Partnership With Gopower